FE-BUS intelligent fire emergency lighting and evacuation instruction system is an intelligent control network system that can real-time monitor the running state of the fire emergency evacuation lamps in the building facilities. The system can obtain the location information of the fire spot quickly and accurately according to the fire alarm linkage signal. Automatic generation evacuation plan, and control of fire emergency lights for evacuation personnel to provide the best evacuation route, to achieve "near evacuation" to "safe evacuation" change.

All the evacuation lamps in the system are made of super bright LED light source through the light guide plate to make the light uniform light. The system host can carry on the uninterrupted inspection to all lamps and lanterns in the system, the sound and light reports the breakdown and shows the specific trouble position, has the standard RS232 / 485 serial communication interface to be connected with the fire alarm system directly, receive the warning place information.
Intelligent fire emergency lighting and evacuation instructions system consists of emergency lighting controller, fire emergency lighting special emergency power, emergency lighting, emergency lighting signs components. Emergency lighting controller through the RS485 bus control fire emergency lighting special emergency power supply, emergency power and lighting between the use of FE-BUS bus communication.
FE-BUS system features
Intelligent fire emergency lighting and evacuation instruction system will be the traditional fire evacuation of the static "near the instructions evacuation" into a dynamic away from the fire, "safe guided evacuation", the "manual inspection" into a "system of intelligent centralized monitoring.
FE-BUS system, all evacuation indicator light is lit, emergency lights only in the emergency state to start. At the same time the host of all evacuation instructions within the system and emergency lighting inspection, inspection of all working conditions within the system, fault information, once the system lights or line failure, the system host can sound and light alarm and accurate positioning Fault location. Maintenance personnel can prompt the system according to the prompt location recovery to ensure that the system is always in a normal working condition, and can greatly reduce manpower maintenance costs.
In the event of fire, the system through the communication interface with the fire alarm system to obtain the fire location information, the system software automatically generates the best escape route, and open the exit lights voice warning, turn off the exit lights, all lights into the system stroboscopic Mode, enhanced evacuation guidance effect. In order to achieve the true sense of the "safe evacuation."
All lamps and lanterns in the system are safe voltage (DC24V) power supply, lamps without batteries, the use of centralized power supply. To avoid the lamp with a battery to bring pollution problems while greatly improving the battery utilization. System uses FE-BUS bus technology, power lines and communication lines can be laid with the pipe, greatly reducing construction costs.
The system software uses the humanized interactive interface design, can accurately display the building plan and the equipment installation position, the operator may through the operation contact surface intuitionistic simple operation software, when the fire happening may be quick according to the scene situation adjustment or the revision evacuation plan.